500 kVA

[WPSM_AC id=662]

Categories: ,

Description

PARAMETERS DG MODELS
Genset Prime Rating (kVA) * 500
Genset Prime Rating (KW) 400
Phase / Voltage (V) 3/415
Power Factor 0.8 (lagging)
Current (A) 695
Frequency (Hz)& RPM 50/1500
Governing class G2
Starting system 24 V DC Electrical
Fuel tank capacity (lit) 700
Genset dimensions w/o silencer (mm) (L x W x H) approx. 5000x1900x2302
Genset Weight (kg) approx. 5800
Engine Specification
Make / Series Perkins
Engine Model 2506D-E15TAG2
Power Output# (Kw) 453
Aspiration Turbo Charged After Cooled
No. of cylinders 6
Bore x Stroke (mm) 137*171
Displacement (Lit) 15.2
Fuel consumption @ 75% load (lit/hr)^ 78.6
Fuel consumption @ 100% load (lit/hr)^ 101
Total lubrication system capacity (lit) 62
Lube oil consumption @ 100% load* 0.1% of fuel consumption
Lube oil change period (hrs.) 500
Radiator coolant capacity (lit) 48
Alternator
Make CG/LS/Stamford
Enclosure Type IP23
Voltage regulation ±1%
Class of insulation Class H
Maximum Unbalanced Load across Phases 25%

 

All Specifications are at Standard NTP operating conditions
^ Considering 0.845 Specific Gravity of diesel, +5 % Tolerance
# Engine Power at 110 % load
Fuel -High Speed diesel (HSD IS 1460:2005)
* Represent the Standby Ratings
$ Considering 0.89 Specific Gravity of Oil
Engine Power will have ± 5 % Tolerance
** For CG only 3 Phase Configuration available
$$Height Without Silencer

Reviews